Strip Footing design check for AS 3600, ACI 318, CSA A23.3 and Eurocode 7
Continuous strip footing under a wall line-load.
Create a free account to use it
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.
What it checks
Bearing pressure, the cantilever face moment and reinforcement, and one-way shear, all per metre run.
Inputs
Strip Footing takes 14 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.
| Input | Unit | Default |
|---|---|---|
| Actions | ||
| Wall line load P* | kN/m | 120 |
| Footing | ||
| Footing width B | m | 1.2 |
| Footing depth D | mm | 400 |
| Wall thickness | mm | 200 |
| Soil | ||
| Allowable bearing | kPa | 200 |
| Material | ||
| Concrete f'c | MPa | 25 |
| fsy | MPa | 500 |
| Reinforcement | ||
| Cover | mm | 60 |
| Bar dia | mm | 16 |
| Bar spacing | mm | 200 |
| Longitudinal bars (bottom, B2): size Options: N10; N12; N16; N20; N24; N28; N32. | - | N12 |
| Longitudinal bars (bottom, B2): spacing across the width | mm | 300 |
| Top longitudinal bars (T1): size Options: N10; N12; N16; N20; N24; N28; N32. | - | N12 |
| Top longitudinal bars (T1): spacing across the width | mm | 250 |
Results and report
The module reports: Bearing pressure q; Neutral axis k_u; Steel; Projection; Face moment; Reinforcement; Shear φVuc.
It checks: Bearing pressure; One-way shear; Flexural capacity (stress-block); Minimum reinforcement; Section ductility k_u (Under-reinforced (ductile)); Tension steel yielding; Maximum reinforcement; Tension steel yielding: under-reinforced, ductile; Minimum reinforcement Ast,min.
Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.
Example with the default inputs
Strip Footing with its default inputs for the Australia and New Zealand code system. The main inputs:
| Input | Value |
|---|---|
| Wall line load P* | 120 kN/m |
| Footing width B | 1.2 m |
| Footing depth D | 400 mm |
| Wall thickness | 200 mm |
| Allowable bearing | 200 kPa |
| Concrete f'c | 25 MPa |
| fsy | 500 MPa |
| Cover | 60 mm |
Headline results:
| Result | Value |
|---|---|
| Bearing pressure q | 109.6 (allow 200) kPa |
| Neutral axis k_u | 0.082 / Under-reinforced (ductile) |
| Steel | yielding ✓ |
| Projection | 0.50 m |
| Face moment | 13.7 kNm/m |
| Reinforcement | 578 mm²/m |
Governing check: Bottom longitudinal bars B2: at least half the minimum distribution steel of B × h at the bottom face (AS 3600:2018 9.4.3 (1.75 × 10⁻³ bD, secondary direction, free to shrink), split equally between the two faces), required 420 mm² against provided N12 at 300 mm = 452 mm², utilisation 0.93, passes.
Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.
Design codes
Strip Footing works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.
| Region | Standard and edition |
|---|---|
| Australia and New Zealand | AS 3600:2018 |
| United States | ACI CODE-318-25 |
| Canada | CSA A23.3-19 |
| Europe | EN 1997-1:2004+A1:2013, EN 1992-1-1:2004+A1:2014, EN 1990:2002+A1:2005 |
This module is one of the 21 basic calculators of the Free plan (one code system, reports carry an Evaluation mark), and it opens fully during the 7-day trial. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.
Related modules
- Bored Pier
Bored (CFA/cast-in-situ) pier - Combined Footing
Combined footing supporting two columns - Eccentric Pad
Eccentrically-loaded pad footing - Pad Foundation
Factored loading with eccentricity, uplift, sliding and overturning; two-way reinforcement by mesh (SL/RL) or bar diameter + spacing. - Piered Beam
Reinforced-concrete ground beam spanning between bored piers - Post Footing
Embedded post footing driven by lateral load, applied moment, load height, footing width/depth and soil φ/γ (embedment depth governs). - Tree Effects: Piers
Bored pier through a tree-affected reactive (drying/swelling) zone - Basement Wall
Basement wall