Combined Footing design check for AS 3600, ACI 318, CSA A23.3 and Eurocode 7
Combined footing supporting two columns.
Create a free account to use it
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.
What it checks
The uniform bearing pressure, the longitudinal beam moments (hogging at the columns, sagging between), the transverse cantilever moment and the one-way shear, with reinforcement.
Inputs
Combined Footing takes 16 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.
| Input | Unit | Default |
|---|---|---|
| Loads | ||
| Column 1 load N1* | kN | 600 |
| Column 2 load N2* | kN | 800 |
| Geometry | ||
| Column spacing | m | 4 |
| Overhang past col 1 | m | 0.6 |
| Overhang past col 2 | m | 0.6 |
| Total footing length (0 = auto: overhangs + spacing) | m | 0 |
| Footing | ||
| Footing width B | m | 2.5 |
| Footing depth D | mm | 750 |
| Soil | ||
| Allowable bearing | kPa | 250 |
| Material | ||
| Concrete f'c | MPa | 32 |
| fsy | MPa | 500 |
| Reinforcement | ||
| Cover | mm | 70 |
| Longit. bar dia | mm | 20 |
| Longit. spacing | mm | 150 |
| Trans. bar dia | mm | 20 |
| Trans. spacing | mm | 200 |
Results and report
The module reports: Footing length L; Bearing pressure q; Longitudinal moment (gov); Transverse moment; Long. reinforcement.
It checks: Bearing pressure; One-way shear (longitudinal); Long Flexural capacity (stress-block); Long Minimum reinforcement; Long Section ductility k_u (Under-reinforced (ductile)); Long Tension steel yielding; Long Maximum reinforcement; Trans Flexural capacity (stress-block); Trans Minimum reinforcement; Trans Section ductility k_u (Under-reinforced (ductile)).
Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.
Example with the default inputs
Combined Footing with its default inputs for the Australia and New Zealand code system. The main inputs:
| Input | Value |
|---|---|
| Column 1 load N1* | 600 kN |
| Column 2 load N2* | 800 kN |
| Column spacing | 4 m |
| Overhang past col 1 | 0.6 m |
| Overhang past col 2 | 0.6 m |
| Total footing length (0 = auto: overhangs + spacing) | 0 m |
| Footing width B | 2.5 m |
| Footing depth D | 750 mm |
Headline results:
| Result | Value |
|---|---|
| Footing length L | 5.20 m |
| Bearing pressure q | 126 kPa |
| Longitudinal moment (gov) | 309 kNm |
| Transverse moment | 69 kNm/m |
| Long. reinforcement | 5236 mm² |
Governing check: Trans Minimum reinforcement (AS 3600 §8.1.6), Ast,min 1175 mm²/m against Ast 1571 mm²/m, utilisation 0.75, passes.
Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.
Design codes
Combined Footing works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.
| Region | Standard and edition |
|---|---|
| Australia and New Zealand | AS 3600:2018 |
| United States | ACI CODE-318-25 |
| Canada | CSA A23.3-19 |
| Europe | EN 1997-1:2004+A1:2013, EN 1992-1-1:2004+A1:2014, EN 1990:2002+A1:2005 |
Use it in full during the 7-day trial of the Professional plan. Paid plans give access to the module packs. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.
Related modules
- Bored Pier
Bored (CFA/cast-in-situ) pier - Eccentric Pad
Eccentrically-loaded pad footing - Pad Foundation
Factored loading with eccentricity, uplift, sliding and overturning; two-way reinforcement by mesh (SL/RL) or bar diameter + spacing. - Piered Beam
Reinforced-concrete ground beam spanning between bored piers - Post Footing
Embedded post footing driven by lateral load, applied moment, load height, footing width/depth and soil φ/γ (embedment depth governs). - Strip Footing
Continuous strip footing under a wall line-load - Tree Effects: Piers
Bored pier through a tree-affected reactive (drying/swelling) zone - Basement Wall
Basement wall
Open Combined Footing with a free account
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.