Basement Wall design check for AS 3600, ACI 318, CSA A23.3 and Eurocode 2

Basement wall.

Create a free account to use it

7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.

What it checks

RC wall panel embedded within a structure (basement), propped at top (floor slab/beam) and base (footing).

Inputs

Basement Wall takes 12 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.

InputUnitDefault
Retained height Hm2.7
Wall thickness twmm250
Wall support condition Options: Propped (floor slab at top + base); Cantilever (base fixed only).-Propped (floor slab at top + base)
Soil unit weight γkN/m³18
Friction angle φ°30
Surcharge qkPa5
Water depth at basem0
Concrete f'cMPa32
fsyMPa500
Covermm40
Bar diamm16
Bar spacingmm200

Results and report

The module reports: Neutral axis k_u; Stem steel; Active coefficient Ka; Total thrust Ptot; Design moment Mmax; Reinforcement; Shear φVuc.

It checks: One-way shear; Flexural capacity (stress-block); Minimum reinforcement; Section ductility k_u (Under-reinforced (ductile)); Tension steel yielding; Maximum reinforcement; Tension steel yielding: under-reinforced, ductile; Minimum reinforcement Ast,min.

Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.

Example with the default inputs

Basement Wall with its default inputs for the Australia and New Zealand code system. The main inputs:

InputValue
Retained height H2.7 m
Wall thickness tw250 mm
Wall support conditionPropped (floor slab at top + base)
Soil unit weight γ18 kN/m³
Friction angle φ30 °
Surcharge q5 kPa
Water depth at base0 m
Concrete f'c32 MPa

Headline results:

ResultValue
Neutral axis k_u0.109 / Under-reinforced (ductile)
Stem steelyielding ✓
Active coefficient Ka0.333
Total thrust Ptot26.4 kN/m
Design moment Mmax9.1 kNm/m
Reinforcement- mm²/m

Governing check: Minimum reinforcement (AS 3600 §8.1.6), Ast,min 420 mm²/m against Ast 1005 mm²/m, utilisation 0.42, passes.

Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.

Design codes

Basement Wall works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.

RegionStandard and edition
Australia and New ZealandAS 3600:2018
United StatesACI CODE-318-25
CanadaCSA A23.3-19
EuropeEN 1992-1-1:2004+A1:2014, EN 1997-1:2004+A1:2013

Use it in full during the 7-day trial of the Professional plan. Paid plans give access to the module packs. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.

Related modules

All foundation design modules

Open Basement Wall with a free account

7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.