Pad Foundation design check for AS 3600, ACI 318, CSA A23.3 and Eurocode 7
Pad Foundation is a module of the footings group, for Australia and New Zealand, United States, Canada and Europe.
Create a free account to use it
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.
What it checks
Factored loading with eccentricity, uplift, sliding and overturning; two-way reinforcement by mesh (SL/RL) or bar diameter + spacing.
Inputs
Pad Foundation takes 16 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.
| Input | Unit | Default |
|---|---|---|
| Loads | ||
| Axial N* (factored) | kN | 1040 |
| Moment M*x | kNm | 80 |
| Horizontal H* | kN | 60 |
| Uplift T* | kN | 0 |
| Geometry | ||
| Width B | m | 2.4 |
| Length L | m | 2.4 |
| Depth | m | 0.5 |
| Column size | m | 0.5 |
| Soil | ||
| Allowable bearing | kPa | 250 |
| Base friction μ | - | 0.5 |
| Materials | ||
| f'c | MPa | 32 |
| fsy | MPa | 500 |
| Reinforcement | ||
| Reinforcement type Options: Bars; Mesh (SL/RL). | - | Bars |
| Bar diameter | mm | 16 |
| Bar spacing | mm | 200 |
| Cover | mm | 50 |
Results and report
The module reports: Self + soil weight; Eccentricity e; Max bearing qmax; Min bearing qmin; Sliding resistance μN; Overturning resistance; Reo required (≥min); Reo provided.
It checks: Bearing pressure; Overturning; Flexural capacity (stress-block); Minimum reinforcement; Section ductility k_u (Under-reinforced (ductile)); Tension steel yielding; Maximum reinforcement; Tension steel yielding: under-reinforced, ductile; Minimum reinforcement Ast,min.
Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.
Example with the default inputs
Pad Foundation with its default inputs for the Australia and New Zealand code system. The main inputs:
| Input | Value |
|---|---|
| Axial N* (factored) | 1040 kN |
| Moment M*x | 80 kNm |
| Horizontal H* | 60 kN |
| Uplift T* | 0 kN |
| Width B | 2.4 m |
| Length L | 2.4 m |
| Depth | 0.5 m |
| Column size | 0.5 m |
Headline results:
| Result | Value |
|---|---|
| Self + soil weight | 69.1 kN |
| Eccentricity e | 0.072 m |
| Max bearing qmax | 227.3 kPa |
| Min bearing qmin | 157.8 kPa |
| Sliding resistance μN | 554.6 kN |
| Overturning resistance | 1330.9 kNm |
Governing check: Bearing pressure (AS 2159), q_max 227.3 kPa against 250.0 kPa, utilisation 0.91, passes.
Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.
Design codes
Pad Foundation works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.
| Region | Standard and edition |
|---|---|
| Australia and New Zealand | AS 3600:2018, AS 2159:2009 |
| United States | ACI CODE-318-25 |
| Canada | CSA A23.3-19 |
| Europe | EN 1997-1:2004+A1:2013, EN 1992-1-1:2004+A1:2014, EN 1990:2002+A1:2005 |
This module is one of the 21 basic calculators of the Free plan (one code system, reports carry an Evaluation mark), and it opens fully during the 7-day trial. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.
Related modules
- Bored Pier
Bored (CFA/cast-in-situ) pier - Combined Footing
Combined footing supporting two columns - Eccentric Pad
Eccentrically-loaded pad footing - Piered Beam
Reinforced-concrete ground beam spanning between bored piers - Post Footing
Embedded post footing driven by lateral load, applied moment, load height, footing width/depth and soil φ/γ (embedment depth governs). - Strip Footing
Continuous strip footing under a wall line-load - Tree Effects: Piers
Bored pier through a tree-affected reactive (drying/swelling) zone - Basement Wall
Basement wall
Open Pad Foundation with a free account
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.