Timber Member in Fire design check for AS 1720.4, AWC NDS, CSA O86 and Eurocode 5
Fire resistance of a timber beam or column to AS 1720.4 by the residual section method.
Create a free account to use it
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.
What it checks
Char rate from the timber density or Table 2.5.1, the 7.0 mm uncharred layer of Eq 2.6.1, residual section, and the bending, shear or compression capacity of the residual s.
Inputs
Timber Member in Fire takes 16 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.
| Input | Unit | Default |
|---|---|---|
| Member Options: Beam, laterally restrained (bending and shear); Column (axial compression, pinned ends). | - | Beam, laterally restrained (bending and shear) |
| Fire exposure Options: Four sides; Three sides (top face protected by a deck or slab); One side (bottom face only). | - | Three sides (top face protected by a deck or slab) |
| Width b | mm | 200 |
| Depth d | mm | 450 |
| Span L (beam) or effective length l_e (column) | m | 9 |
| Species and grade Options: F17 seasoned hardwood (values of the AS 1720.1 Timber Member module); Custom: enter characteristic strengths. | - | F17 seasoned hardwood (values of the AS 1720.1 Timber Member module) |
| Required fire resistance (minutes) | - | 60 |
| Seasoned density ρ (kg/m³) | - | 650 |
| Notional charring rate (Table 2.5.1, or Eq 2.5.2 from the density) Options: From the density, Eq 2.5.2; Blackbutt 0.50; Cypress 0.56; Douglas fir (North America, NZ) 0.65; European spruce 0.65; Spotted gum 0.46; Grey ironbark 0.46; Red ironbark 0.47; +4 more. | - | From the density, Eq 2.5.2 |
| Duration factor k_1 for a 5 h load duration (AS 1720.1 Table 2.3: 0.97) | - | 0.97 |
| Application category (AS 1720.1 Table 2.1) Options: Category 1: house members (failure area 25 m² or less) or secondary members; Category 2: primary members in structures other than houses; Category 3: primary members of essential service or post-disaster structures. | - | Category 2: primary members in structures other than houses |
| Permanent action effect G, bending moment | kNm | 35 |
| Imposed action effect Q, bending moment | kNm | 40 |
| Permanent action effect G, shear | kN | 25 |
| Imposed action effect Q, shear | kN | 20 |
| Long-term factor ψ_l (AS/NZS 1170.0 Table 4.1) | - | 0.4 |
Results and report
The module reports: Material; Original section b × d; Fire exposure; Char rate β; Total loss on each exposed face; Residual section b_r × d_r; Residual area A_r; Residual section modulus S_r; Fire design action moment; Capacity of the residual section; Fire design shear; Shear capacity of the residual section.
It checks: Bending of the residual section, E_fi ≤ M_fi; Shear of the residual section, E_fi ≤ V_fi; Fire resistance period (time to failure of the residual section).
Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.
Example with the default inputs
Timber Member in Fire with its default inputs for the Australia and New Zealand code system. The main inputs:
| Input | Value |
|---|---|
| Member | Beam, laterally restrained (bending and shear) |
| Fire exposure | Three sides (top face protected by a deck or slab) |
| Width b | 200 mm |
| Depth d | 450 mm |
| Span L (beam) or effective length l_e (column) | 9 m |
| Species and grade | F17 seasoned hardwood (values of the AS 1720.1 Timber Member module) |
| Required fire resistance (minutes) | 60 |
| Seasoned density ρ (kg/m³) | 650 |
Headline results:
| Result | Value |
|---|---|
| Material | F17 seasoned hardwood (values of the AS 1720.1 Timber Member module) |
| Original section b × d | 200.0 × 450.0 mm |
| Fire exposure | Three sides |
| Char rate β | 0.586 mm/min |
| Char depth x_c at 60 min | 35.1 mm |
| Uncharred layer at elevated temperature (7.0 mm, Eq 2.6.1) | 7.0 mm |
Governing check: Fire resistance period (time to failure of the residual section) (AS 1720.4 and AS 1720.1 Cl. 3.2), 60 min required against 106.7 min, utilisation 0.56, passes.
Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.
Design codes
Timber Member in Fire works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.
| Region | Standard and edition |
|---|---|
| Australia and New Zealand | AS 1720.4:2019 |
| United States | ANSI/AWC NDS-2018 |
| Canada | CSA O86-19 |
| Europe | EN 1995-1-2:2004 |
Use it in full during the 7-day trial of the Professional plan. Paid plans give access to the module packs. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.
Related modules
- Circular Column
Circular timber column / pole to AS 1720.1 §3.3 - F17 Span Tables
Maximum span for an F-grade timber member - Joint
Timber joint (bolted / nailed / screwed) lateral capacity to AS 1720.1 §4 - Timber Column
Timber column/post to AS 1720.1 §3.3 - Timber Floor Beam
Sawn/LVL timber floor beam to AS 1720.1 - Timber Member
Sawn / glulam rectangular timber member to AS 1720.1 - Timber Roof Beam
Timber roof beam/rafter to AS 1720.1