Steel Member in Fire design check for AS 4100, AISC 360, CSA S16 and Eurocode 3
Fire resistance of a steel beam or column to AS 4100:2020 Section 12.
Create a free account to use it
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.
What it checks
Exposed surface area to mass ratio k_sm for three or four sided exposure, limiting temperature T_l = 905 - 690r_f, time to reach T_l for an unprotected member (Cl.
Inputs
Steel Member in Fire takes 13 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.
| Input | Unit | Default |
|---|---|---|
| Section | ||
| Section type Options: Universal beam (UB); Universal column (UC); Parallel flange channel (PFC); Square hollow section (SHS); Rectangular hollow section (RHS); Circular hollow section (CHS). | - | Universal beam (UB) |
| Designation | - | 310UB40.4 |
| Member | ||
| Member Options: Beam, laterally restrained (flexure about the major axis); Column (axial compression, flexural buckling). | - | Beam, laterally restrained (flexure about the major axis) |
| Fire | ||
| Fire exposure Options: Four sided (all faces exposed); Three sided (top face against a slab or wall). | - | Three sided (top face against a slab or wall) |
| Fire protection Options: Unprotected; Protected, contour (spray, intumescent, blanket); Protected, box (board). | - | Protected, contour (spray, intumescent, blanket) |
| Protection thermal conductivity k_p (W/m·K) | - | 0.12 |
| Protection thickness d_p | mm | 20 |
| Protection density ρ_p (kg/m³) | - | 300 |
| Protection specific heat c_p (J/kg·K) | - | 1100 |
| Required fire resistance (minutes) | - | 60 |
| Actions | ||
| Permanent action effect G, bending moment | kNm | 40 |
| Imposed action effect Q, bending moment | kNm | 30 |
| Long-term factor ψ_l (AS/NZS 1170.0 Table 4.1) | - | 0.4 |
Results and report
The module reports: Section; Fire exposure and protection; Heated perimeter P; Section factor A_m/V; Exposed surface area to mass ratio k_sm; k_sm of the protection internal surface; Fire design action E_fi; Ambient design capacity φR_u; Load ratio r_f; Limiting temperature T_l; Time to the limiting temperature; Required fire resistance.
It checks: Fire resistance period (time to the limiting temperature); Strength at the required fire resistance, E_fi ≤ φR_u at the steel temperature; Protected member, heat transfer model.
Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.
Example with the default inputs
Steel Member in Fire with its default inputs for the Australia and New Zealand code system. The main inputs:
| Input | Value |
|---|---|
| Section type | Universal beam (UB) |
| Designation | 310UB40.4 |
| Member | Beam, laterally restrained (flexure about the major axis) |
| Fire exposure | Three sided (top face against a slab or wall) |
| Fire protection | Protected, contour (spray, intumescent, blanket) |
| Protection thermal conductivity k_p (W/m·K) | 0.12 |
| Protection thickness d_p | 20 mm |
| Protection density ρ_p (kg/m³) | 300 |
Headline results:
| Result | Value |
|---|---|
| Section | 310UB40.4 (I) |
| Fire exposure and protection | Three sided, Contour, d_p = 20 mm, k_p = 0.12 W/m·K |
| Heated perimeter P | 1091 mm |
| Section factor A_m/V | 209 1/m |
| Exposed surface area to mass ratio k_sm | 27.0 m²/t |
| k_sm of the protection internal surface | 27.0 m²/t |
Governing check: Fire resistance period (time to the limiting temperature) (AS 4100 12.3 and 12.5), 60 min required against 109.1 min, utilisation 0.55, passes.
Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.
Design codes
Steel Member in Fire works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.
| Region | Standard and edition |
|---|---|
| Australia and New Zealand | AS 4100:2020 |
| United States | ANSI/AISC 360-22 |
| Canada | CSA S16-19 |
| Europe | EN 1993-1-2:2005 |
Use it in full during the 7-day trial of the Professional plan. Paid plans give access to the module packs. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.
Related modules
- Beam-Column
Steel member under combined axial compression and bending to AS 4100 §8 - Composite Member
Simply-supported composite steel-and-concrete beam to AS 2327 - Compression Strut
Axially-loaded steel member (strut / column) to AS 4100 - Crane Beam
Overhead-crane runway beam - Floor Beam
Simply-supported steel floor beam to AS 4100 - Load Stiffener
Load-bearing web stiffener to AS 4100 §5.14 - Mullion
Steel wall mullion / wind post to AS 4100 - PFC & Plate
Built-up beam from a PFC (parallel-flange channel) with a welded plate
Open Steel Member in Fire with a free account
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.