Mullion design check for AS 4100, AISC 360, CSA S16 and Eurocode 3
Steel wall mullion / wind post to AS 4100.
Create a free account to use it
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.
What it checks
A vertical member spanning between floors under lateral wind pressure on its tributary width; checks bending, shear and the (governing) wind deflection.
Inputs
Mullion takes 7 inputs for the Australia and New Zealand code system, with the defaults below. Lengths are in m, forces in kN and stresses in MPa unless the unit column says otherwise.
| Input | Unit | Default |
|---|---|---|
| Section | ||
| Section type Options: PFC; UC; UB; SHS; RHS. | - | PFC |
| Section | - | 250PFC35.5 |
| Geometry | ||
| Height (span) L | m | 4 |
| Lateral restraint Options: Continuous (glazing/cladding); At ends only; Custom Le. | - | At ends only |
| Loads | ||
| Wind pressure w | kPa | 1.2 |
| Tributary width | m | 2 |
| Deflection limit span/ Options: span/120; span/150; span/175; span/250. | - | span/175 |
Results and report
The module reports: Section; Wind UDL w*; Design moment M*; φMbx (member); Wind deflection δ.
It checks: Section moment; Member moment; Wind deflection.
Each module produces a report: numbered working, formulas with substituted values, tables and diagrams, ready to attach to a calculation package. The report carries a verification code that confirms it was made by TensorNode and has not been changed.
Example with the default inputs
Mullion with its default inputs for the Australia and New Zealand code system. The main inputs:
| Input | Value |
|---|---|
| Section type | PFC |
| Section | 250PFC35.5 |
| Height (span) L | 4 m |
| Lateral restraint | At ends only |
| Wind pressure w | 1.2 kPa |
| Tributary width | 2 m |
| Deflection limit span/ | span/175 |
Headline results:
| Result | Value |
|---|---|
| Section | 250PFC35.5 (PFC) |
| Wind UDL w* | 2.40 kN/m |
| Design moment M* | 4.8 kNm |
| φMbx (member) | 61.0 kNm |
| Wind deflection δ | 0.9 (limit 22.9) mm |
Governing check: Member moment (AS 4100 §5.6), M* 4.8 kNm against φMbx 61.0 kNm, utilisation 0.08, passes.
Computed by TensorNode with the default inputs shown; a qualified engineer checks every result.
Design codes
Mullion works to 4 code systems in Australia and New Zealand, United States, Canada and Europe. The standards and editions are listed below; clause numbers are cited in the report.
| Region | Standard and edition |
|---|---|
| Australia and New Zealand | AS 4100:2020 |
| United States | ANSI/AISC 360-22 |
| Canada | CSA S16-19 |
| Europe | EN 1993-1-1:2005+A1:2014, EN 1990:2002+A1:2005, EN 1991-1-4:2005+A1:2010 |
Use it in full during the 7-day trial of the Professional plan. Paid plans give access to the module packs. TensorNode is a calculation aid. Every result must be checked and accepted by a qualified engineer, who remains responsible for the design. Read the scope and limits of this module before you rely on a result.
Related modules
- Beam-Column
Steel member under combined axial compression and bending to AS 4100 §8 - Compression Strut
Axially-loaded steel member (strut / column) to AS 4100 - Crane Beam
Overhead-crane runway beam - Floor Beam
Simply-supported steel floor beam to AS 4100 - Load Stiffener
Load-bearing web stiffener to AS 4100 §5.14 - PFC & Plate
Built-up beam from a PFC (parallel-flange channel) with a welded plate - Portal Frame
Single-bay portal frame to AS 4100 - Propped Beam
Steel propped cantilever to AS 4100
Open Mullion with a free account
7 days of the Professional plan, no card. After the trial the account moves to the Free plan; nothing is charged automatically.